Anderson Jose Beber, Ind Chem 2017, 3:2 (Suppl)

http://dx.doi.org/10.4172/2469-9764-C1-005

Reduction on water consumption on a cooling tower with the application of a novel biocide

Anderson Jose Beber

Solenis Water Technologies, Brazil

M

icrobiological control is essential in any cooling water system. A cooling system such as a large cooling tower is an

excellent environment for microbiological growth: Water, warm temperature, oxygen, dust and debris from air, nutrients

and others are some of the variables that contribute largely to the growth of microbiology colonies. The main negative

consequence is that the biofilm (sludge) formed is highly insulating. It is known that biofilm is more insulating that CaCO

3

or

SiO

2

scales. The best and less expensive way to control MB is by using large amounts of oxidizing biocides like chlorine gas,

hypochlorite, bromine, chlorine dioxide. The goal is to maintain an oxidizing environment which is not friendly for bio cells.

However, strong oxidizer may cause high chloride content, lower concentration cycles, higher cost among others. Also, a high

oxidant environment may lead to higher corrosion rates. And finally the strong oxidizers are not selective, reacting to any

contamination not only MB. This paper shows the results of the application of a novel mild oxidizer on a large cooling tower

at a power plant. This specific cooling tower utilizes grey water (tertiary treated domestic sewage) as make up water. After the

application of this mild oxidizer, the concentration cycles were enhanced from an average of 4 up to 6.5, resulting in large

savings to the plant. Also, stainless steel corrosion rates dropped significantly due to the reduction of chlorides and sulfates

residuals.

Biography

Anderson Jose Beber has over 17 year of experience in industrial water treatment, especially clarification, demineralization, reverse osmosis, low and high pressure

boiler water treatment and cooling water treatment. He has worked for different multinational water treatment companies, servicing several industries: Pulp and

paper, power, steel, manufacturing, food and beverage, automotive and many others. Over the past 6 years, he has dedicated his expertise on special projects and

technical assistance to Solenis sales team, being responsible for new product launch, technical training, project development, consultancy for boiler and cooling

water treatment for industries in Latin America.